Precautions for the maintenance and repair of evaporators

Category:


Maintenance and Repair of Evaporators (1) Maintenance of Evaporators 1) Regularly perform leak detection on the evaporator. Leakage is a common fault in evaporators, so frequent leak checks should be conducted during use. When an ammonia evaporator leaks, there is a pungent odor, and the leak area does not frost. Phenolphthalein test paper can be used to check the leak because ammonia is alkaline and turns the test paper red. Visually, the leak point is usually where there is no frost on the evaporator. Soap water can also be used to find leaks. For Freon evaporators, leak detection can be done using a halogen lamp and halogen leak detector, or by using soap water to find leaks. During inspection, first visually check the evaporator

  Maintenance and Repair of Evaporators (1) Maintenance of Evaporators 1) Regularly perform leak detection on the evaporator. Leakage is a common fault in evaporators, so frequent leak checks should be conducted during use. When an ammonia evaporator leaks, there is a pungent odor, and the leak point does not frost.

  Phenolphthalein test paper can be used to check leak points because ammonia is alkaline and turns phenolphthalein paper red. Visually, areas on the evaporator where frost does not form are usually leak points. Soap water can also be used to find leaks. For Freon evaporators, halogen lamps and halogen leak detectors can be used, or soap water can be applied to find leaks.

  During inspection, first visually check for oil stains on the evaporator tubes because Freon and oil are miscible; when Freon leaks, oil also seeps out at the leak point. Therefore, where there is oil, there is a leak. When using a halogen lamp for leak detection, if Freon leaks at a certain point, the flame color changes from blue to light green, grass green, purple-green, purple, etc., indicating the amount of Freon leakage. If the flame is dark green or purple, the phosgene in the flame is toxic, so this method should not be used for long periods. In such cases, soap water should be used to check for leaks. For very small leaks, a halogen leak detector should be used.

  2) Regularly check the frosting condition of the evaporator. When the frost layer is too thick, defrosting should be done promptly. Abnormal frosting may be caused by blockages, which should be identified and eliminated in time. 3) When the evaporator is to be shut down for a long time, refrigerant should be pumped into the liquid receiver or condenser to keep the evaporator pressure around 0.05 MPa (gauge pressure). For evaporators in brine tanks, rinse with tap water and then fill the tank with tap water after rinsing. 4) For evaporators in chillers, ensure the quality of chilled water. Chilled water should be treated softened water. If scale forms when using tap water, descaling treatment should be performed.

  (2) Repair of Evaporators 1) Maintenance of Ammonia Evaporators. The main faults of ammonia evaporators are: internal blockage of pipes due to oil and dirt accumulation; external cracks or pinholes caused by corrosion and other factors.

  ① Blockage. If oil and mechanical impurities mix inside the evaporator, causing high viscosity and blocking the pipes, first perform hot ammonia defrosting. If defrosting does not solve the problem, evacuate the ammonia from the evaporator, then blow out with compressed air at 0.6 MPa (gauge pressure). If blowing does not solve the problem, it indicates there are solid blockages inside the pipe, such as wooden plugs, sandpaper, cotton yarn left inside. Generally, pipe cutting is required. To reduce the number of cuts, locate the blockage by observing frosting before and after the pipe, or by listening for liquid flow sounds indicating throttling. After locating the blockage, cut the pipe, remove the blockage, weld the pipe, and after pressure testing and leak checking, the evaporator can be put back into use.

  ② Leak Repair. If there is a leak in the evaporator tubes, such as pinholes on smooth wall tubes or top tubes, welding repair should be done. If welding cannot be done immediately due to busy production, temporarily block the leak with a rubber sheet secured by pipe clamps, and perform welding during the off-season. If the finned tubes of the air cooler leak, close the air cooler's liquid inlet and suction valves, open the hot ammonia defrost liquid return valve and the defrost liquid return main valve, use a circulation or drainage bucket to evacuate, and open defrost water to increase pressure for faster and cleaner evacuation. Do not use the method of opening the suction valve to evacuate, as it takes longer and ammonia liquid is hard to remove. After evacuation, disconnect relevant connections to atmosphere and perform welding repair with electric or gas welding. If valve internal leakage prevents full evacuation but pressure below atmospheric can be reached, use a punch to enlarge the pinhole until no ammonia leaks, then weld with electric welding. This method is only suitable for equipment used less than 5 years without severe corrosion. Electric welding must be used, not gas welding.

  2) Repair of Freon Evaporators:

  ① Excessive Oil Contamination. Freon can dissolve with lubricating oil, so during refrigerant circulation, lubricating oil inevitably adheres to the inner surface of pipes, especially if design or installation is improper, causing more oil accumulation inside evaporator tubes, which affects heat transfer and ultimately the refrigeration system's performance. During repair, evacuate the refrigerant from the evaporator, disconnect the supply and suction pipe joints, connect a nitrogen cylinder or air compressor, and blow out oil and other impurities with nitrogen or compressed air. If excessive oil is blown out, it indicates poor oil return in the evaporator, possibly due to lack of oil return bends at the end of each evaporator tube set, oversized suction pipe diameter, insufficient flow velocity, or horizontal suction main pipe not sloping toward the machine. Repair accordingly based on the situation.

  ① Blockage. If the evaporator is blocked by oil, mechanical impurities, or even wooden plugs and cotton yarn, repair can be done following the ammonia evaporator maintenance method. ② Leakage. If there is leakage at system connection pipes or evaporator tube unions, tighten with a wrench. If no looseness is found, remove the nut and check if the flare is skewed or damaged, or if the bolt threads are damaged. If the flare is damaged, cut off the flare with a pipe cutter and re-flare it. Ensure the flaring tool is properly aligned; otherwise, the flare will be skewed and leak after assembly. The repair method for steel pipe leaks is the same as welding repair for ammonia evaporators.

Hot News


Evaporator Working Principle

Evaporator working principle: The heating chamber provides the heat required for evaporation to the liquid, causing the liquid to boil and vaporize; the evaporation chamber completely separates the gas and liquid phases. The vapor generated in the heating chamber carries a large amount of liquid droplets. When it reaches the larger space of the evaporation chamber, these liquids are separated from the vapor through their own condensation or the action of demisters. Usually, the demister is installed at the top of the evaporation chamber. According to the movement of the solution in the evaporator, there are: Circulation type. The boiling solution passes multiple times over the heating surface in the heating chamber, such as central circulation tube type, basket type, external heating type, Lewen type, and forced circulation type. Single pass type. The boiling solution in the heating chamber...

2018-09-28


7 Practical Heat Exchanger Technical Q&A

1. How does a heat exchanger transfer heat? Answer: In the most common wall-type heat exchanger, the main heat transfer methods are conduction and convection. The hot fluid first transfers heat to one side of the tube wall by convection, then the heat is conducted through the tube wall to the other side, and finally, the heat is transferred from the other side of the tube wall to the cold fluid by convection, thus completing the heat transfer process of the heat exchanger. 2. How does the flow velocity of the medium affect the heat transfer effect? Answer: The higher the flow velocity of the medium inside the heat exchanger, the greater the heat transfer coefficient. Therefore, increasing the flow velocity of the medium inside the heat exchanger can greatly improve the heat transfer effect.

2018-09-28


What are the functions of water purifier filters? What impurities can they filter out?

How important is the filter cartridge of a water purifier? Those who have bought a water purifier know that sellers always remind us to replace the filter cartridge regularly and timely. This is because after using the filter cartridge for a certain period, it will consume itself continuously due to filtering too many impurities until it reaches the end of its life. So, what exactly are the functions of the water purifier's filter cartridge? What can it filter? What are the functions of the water purifier filter cartridge? What impurities can it filter? Below, we will introduce the functions of the commonly used reverse osmosis water purifier filter cartridge. Generally speaking, the reverse osmosis water purifier has 5 stages of filter cartridges, which we will understand one by one below.

2018-09-28


How to recover the refrigerant from an industrial chiller to the receiver?

During the maintenance or servicing of industrial chillers, it is necessary to recover the refrigerant before proceeding with subsequent maintenance work. There are two common methods for recovering refrigerant from industrial chillers: one is to recover the refrigerant into a receiver, and the other is to recover it into a refrigerant cylinder. 1. How to recover the refrigerant from an industrial chiller into a receiver? Note: Our industrial chillers are equipped with high/low pressure controllers. When recovering refrigerant, the contacts of the high/low pressure controllers should be kept normally closed to prevent the machine from shutting down due to pressure issues during refrigerant recovery. The refrigerant of the industrial chiller should be...

2018-09-28